PVC Schedule 80 Conduit Fill Chart
PVC Schedule 80 (NEC Article 352) has a thicker wall than Schedule 40, so it holds fewer wires in the same trade size. The tables show the most wires that fit in each trade size at the NEC 2026 fill limit.
Updated
For reference only. Always verify with the NEC edition adopted by your AHJ.
PVC Schedule 80 fill: THHN / THWN-2
| Wire size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" | 5" | 6" |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 9 | 17 | 28 | 51 | 70 | 118 | 170 | 265 | 358 | 464 | 736 | 1055 |
| #12 | 6 | 12 | 20 | 37 | 51 | 86 | 124 | 193 | 261 | 338 | 537 | 770 |
| #10 | 4 | 7 | 13 | 23 | 32 | 54 | 78 | 122 | 164 | 213 | 338 | 485 |
| #8 | 1 | 4 | 7 | 13 | 18 | 31 | 45 | 70 | 95 | 123 | 195 | 279 |
| #6 | 1 | 3 | 5 | 9 | 13 | 22 | 32 | 51 | 68 | 89 | 141 | 202 |
| #4 | 1 | 1 | 3 | 6 | 8 | 14 | 20 | 31 | 42 | 54 | 86 | 124 |
| #3 | 1 | 1 | 3 | 5 | 7 | 12 | 17 | 26 | 35 | 46 | 73 | 105 |
| #2 | — | 1 | 1 | 4 | 6 | 10 | 14 | 22 | 30 | 39 | 61 | 88 |
| #1 | — | 1 | 1 | 3 | 4 | 7 | 10 | 16 | 22 | 29 | 45 | 65 |
| #1/0 | — | 1 | 1 | 2 | 3 | 6 | 9 | 14 | 18 | 24 | 38 | 55 |
| #2/0 | — | — | 1 | 1 | 3 | 5 | 7 | 11 | 15 | 20 | 32 | 46 |
| #3/0 | — | — | 1 | 1 | 1 | 4 | 6 | 9 | 13 | 17 | 26 | 38 |
| #4/0 | — | — | 1 | 1 | 1 | 3 | 5 | 8 | 10 | 14 | 22 | 31 |
| 250 kcmil | — | — | — | 1 | 1 | 3 | 4 | 6 | 8 | 11 | 18 | 25 |
| 300 kcmil | — | — | — | 1 | 1 | 1 | 3 | 5 | 7 | 9 | 15 | 22 |
| 350 kcmil | — | — | — | 1 | 1 | 1 | 3 | 5 | 6 | 8 | 13 | 19 |
| 400 kcmil | — | — | — | 1 | 1 | 1 | 3 | 4 | 6 | 7 | 12 | 17 |
| 500 kcmil | — | — | — | — | 1 | 1 | 1 | 3 | 5 | 6 | 10 | 14 |
— means a single conductor of that size does not fit.
PVC Schedule 80 fill: XHHW-2
| Wire size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" | 5" | 6" |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 6 | 11 | 19 | 35 | 49 | 82 | 118 | 185 | 250 | 324 | 514 | 736 |
| #12 | 4 | 9 | 15 | 27 | 38 | 63 | 91 | 142 | 192 | 248 | 394 | 565 |
| #10 | 3 | 6 | 11 | 20 | 28 | 47 | 68 | 106 | 143 | 185 | 294 | 421 |
| #8 | 1 | 3 | 6 | 11 | 15 | 26 | 37 | 59 | 79 | 103 | 163 | 234 |
| #6 | 1 | 2 | 4 | 8 | 11 | 19 | 28 | 43 | 59 | 76 | 121 | 173 |
| #4 | 1 | 1 | 3 | 6 | 8 | 14 | 20 | 31 | 42 | 55 | 87 | 125 |
| #3 | 1 | 1 | 3 | 5 | 7 | 12 | 17 | 26 | 36 | 47 | 74 | 106 |
| #2 | 1 | 1 | 1 | 4 | 6 | 10 | 14 | 22 | 30 | 39 | 62 | 89 |
| #1 | — | 1 | 1 | 3 | 4 | 7 | 10 | 16 | 22 | 29 | 46 | 66 |
| #1/0 | — | 1 | 1 | 2 | 3 | 6 | 9 | 14 | 19 | 24 | 39 | 56 |
| #2/0 | — | — | 1 | 1 | 3 | 5 | 7 | 11 | 16 | 20 | 32 | 46 |
| #3/0 | — | — | 1 | 1 | 2 | 4 | 6 | 9 | 13 | 17 | 27 | 38 |
| #4/0 | — | — | 1 | 1 | 1 | 3 | 5 | 8 | 11 | 14 | 22 | 32 |
| 250 kcmil | — | — | — | 1 | 1 | 3 | 4 | 6 | 9 | 11 | 18 | 26 |
| 300 kcmil | — | — | — | 1 | 1 | 1 | 3 | 5 | 7 | 10 | 15 | 22 |
| 350 kcmil | — | — | — | 1 | 1 | 1 | 3 | 5 | 6 | 8 | 14 | 20 |
| 400 kcmil | — | — | — | 1 | 1 | 1 | 3 | 4 | 6 | 7 | 12 | 17 |
| 500 kcmil | — | — | — | — | 1 | 1 | 1 | 3 | 5 | 6 | 10 | 14 |
— means a single conductor of that size does not fit.
PVC Schedule 80 fill: THW
| Wire size | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" | 5" | 6" |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| #14 | 6 | 11 | 19 | 35 | 49 | 82 | 118 | 185 | 250 | 324 | 514 | 736 |
| #12 | 4 | 9 | 15 | 27 | 38 | 63 | 91 | 142 | 192 | 248 | 394 | 565 |
| #10 | 3 | 6 | 11 | 20 | 28 | 47 | 68 | 106 | 143 | 185 | 294 | 421 |
| #8 | 1 | 3 | 6 | 11 | 15 | 26 | 37 | 59 | 79 | 103 | 163 | 234 |
| #6 | 1 | 1 | 3 | 7 | 9 | 16 | 22 | 35 | 48 | 62 | 98 | 141 |
| #4 | 1 | 1 | 3 | 5 | 7 | 12 | 17 | 26 | 35 | 46 | 73 | 105 |
| #3 | 1 | 1 | 1 | 4 | 6 | 10 | 14 | 22 | 30 | 39 | 63 | 90 |
| #2 | — | 1 | 1 | 3 | 5 | 8 | 12 | 19 | 26 | 33 | 53 | 77 |
| #1 | — | 1 | 1 | 2 | 3 | 6 | 8 | 13 | 18 | 23 | 37 | 54 |
| #1/0 | — | — | 1 | 1 | 3 | 5 | 7 | 11 | 15 | 20 | 32 | 46 |
| #2/0 | — | — | 1 | 1 | 2 | 4 | 6 | 10 | 13 | 17 | 27 | 39 |
| #3/0 | — | — | 1 | 1 | 1 | 3 | 5 | 8 | 11 | 14 | 23 | 33 |
| #4/0 | — | — | — | 1 | 1 | 3 | 4 | 7 | 9 | 12 | 19 | 27 |
| 250 kcmil | — | — | — | 1 | 1 | 1 | 3 | 5 | 7 | 9 | 15 | 22 |
| 300 kcmil | — | — | — | 1 | 1 | 1 | 3 | 5 | 6 | 8 | 13 | 19 |
| 350 kcmil | — | — | — | 1 | 1 | 1 | 2 | 4 | 6 | 7 | 12 | 17 |
| 400 kcmil | — | — | — | — | 1 | 1 | 1 | 4 | 5 | 7 | 10 | 15 |
| 500 kcmil | — | — | — | — | 1 | 1 | 1 | 3 | 4 | 5 | 9 | 13 |
— means a single conductor of that size does not fit.
Pick a trade size
PVC Schedule 80 conduit fill questions
- How many #12 THHN wires fit in 1/2" PVC Schedule 80 conduit?
- Up to 6 #12 THHN/THWN-2 conductors fit in 1/2" PVC Schedule 80 under NEC 2026 Chapter 9 (40% fill for three or more wires).
- How many #12 THHN wires fit in 3/4" PVC Schedule 80 conduit?
- Up to 12 #12 THHN/THWN-2 conductors fit in 3/4" PVC Schedule 80 under NEC 2026 Chapter 9 (40% fill for three or more wires).
- How many #12 THHN wires fit in 1" PVC Schedule 80 conduit?
- Up to 20 #12 THHN/THWN-2 conductors fit in 1" PVC Schedule 80 under NEC 2026 Chapter 9 (40% fill for three or more wires).
- What is the fill limit for PVC Schedule 80?
- The same NEC 2026 Chapter 9 Table 1 limits apply to every raceway: 53% of the inside area for one wire, 31% for two and 40% for three or more. PVC Schedule 80 only changes the inside area, from Table 4.
- Does a short PVC Schedule 80 nipple get more fill?
- Yes. Chapter 9 Note 4 allows 60% fill for a nipple 24 inches or shorter between boxes or enclosures. The chart above uses the normal limits.