NEC 2026

15 Amp Wire Size

What size wire for a 15 A load? The answer depends on terminations, continuous load and conductor material. Both 60 °C and 75 °C answers, under NEC 2026.

Updated

For reference only. Always verify with the NEC edition adopted by your AHJ.

Wire size for a 15 A load

The answer depends on the terminations. Under 110.14(C)(1), circuits of 100 A or less, and 14-1 AWG conductors, default to the 60 °C column of Table 310.16. Use the 75 °C answer only if all terminations are listed/marked for 75 °C. Both are for 90 °C insulation (such as THHN), 30 °C ambient and no more than 3 current-carrying conductors.

Smallest conductor for a 15 A noncontinuous load
Conductor60 °C terminations75 °C terminations
Copper#14 AWGMax OCPD 15A (240.4(D))#14 AWGMax OCPD 15A (240.4(D))
Aluminum#12 AWGMax OCPD 15A (240.4(D))#12 AWGMax OCPD 15A (240.4(D))

If 15 A is a continuous load

A continuous load runs three hours or more. 210.19(A)(1) and 215.4(A)(1) size the conductor at 125%, so 15 A becomes 18.75 A. The overcurrent device is sized to the same 125%, so it will be larger than 15 A.

Smallest conductor for a 15 A continuous load
Conductor60 °C terminations75 °C terminations
Copper#12 AWGMax OCPD 20A (240.4(D))#12 AWGMax OCPD 20A (240.4(D))
Aluminum#10 AWGMax OCPD 25A (240.4(D))#10 AWGMax OCPD 25A (240.4(D))

What these answers leave out

  • Small conductors have a breaker cap. Under 240.4(D), overcurrent protection is limited to 30 A for 10 AWG copper, 20 A for 12 AWG copper, 15 A for 14 AWG copper, 25 A for 10 AWG aluminum, 15 A for 12 AWG aluminum. Where it applies, the table shows it as Max OCPD.
  • Ambient above 30 °C (310.15(B)(1)) and more than 3 current-carrying conductors (310.15(C)(1)) reduce ampacity and can raise the size. Use the calculator to include them.
  • Voltage drop is not included; long runs may need a larger conductor.

15 amp wire size questions

What size wire is needed for a 15 A load?
It depends on the conductor and the terminations. For a 15 A noncontinuous load in copper (90 °C insulation, 30 °C ambient, 3 or fewer current-carrying conductors): #14 AWG when the terminations are limited to 60 °C, and #14 AWG only if all terminations are listed/marked for 75 °C (110.14(C)(1)). In aluminum: #12 AWG at 60 °C and #12 AWG at 75 °C. Voltage drop is not included; long runs may need a larger conductor.
Does a continuous load change the wire size for 15 amps?
Yes. A continuous load (3 hours or more) is sized at 125% under 210.19(A)(1) and 215.4(A)(1), so 15 A becomes 18.75 A. In copper that is #12 AWG at 60 °C and #12 AWG at 75 °C. The overcurrent device must be sized to the same 125%, so it is larger than 15 A.
Does 240.4(D) limit a 15 A load?
Yes for the smallest sizes. Under 240.4(D), conductors cannot be protected above 30 A for 10 AWG copper, 20 A for 12 AWG copper, 15 A for 14 AWG copper, 25 A for 10 AWG aluminum, 15 A for 12 AWG aluminum, so a 15 A load cannot use one that is capped lower.
Why does the 15 A answer depend on 60 °C or 75 °C?
110.14(C) limits the ampacity to the lowest temperature rating of the conductor and its terminations. Circuits of 100 A or less, and 14-1 AWG conductors, default to the 60 °C column unless the equipment is marked for 75 °C, so the 60 °C answer is the safe default and the 75 °C answer needs every termination to be listed for it.

You can read the NEC 2026 for free at NFPA free access. Need another load? Use the wire size calculator.