125 Amp Service Wire Size

What size conductors does a 125 amp dwelling service need? The 310.12 answer for 120/240 V single-phase, next to the plain Table 310.16 size, under NEC 2023 & 2026.

Updated

NEC edition

Values are the same in NEC 2023 and NEC 2026. 215.2(A)(1) in 2023, 215.4(A)(1) in 2026.

For reference only. Always verify with the NEC edition adopted by your AHJ.

Wire size for a 125 amp service

This page applies 310.12 to a 120/240 V single-phase dwelling service that carries the entire load of a dwelling unit. That rule sizes the conductors at 83% of the 125 A rating, 103.75 A, using the 75 °C column of Table 310.16. It does not apply to commercial, three-phase or multifamily services.

Dwelling service conductors for a 125 A service
Conductor310.12 (83%)Table 310.16, 75 °C, full 125 A
Copper#2 AWG#1 AWG
Aluminum1/0 AWG2/0 AWG

What this answer leaves out

  • No ambient (310.15(B)(1)) or conductor-count (310.15(C)(1)) correction is applied. Hot locations or bundled conductors need their own calculation.
  • The 310.12 result assumes the service and meter terminations are listed or marked for 75 °C (110.14(C)). If any terminal is rated 60 °C, the conductor may need to be larger; for example #4 copper is 70 A at 60 °C against 85 A at 75 °C.
  • Grounded (neutral) and grounding conductors have their own sizing rules; this is not an answer for them.
  • Voltage drop is not included; long runs may need a larger conductor.

125 amp wire size questions

What size wire is needed for a 125 amp service?
For a 120/240 V single-phase dwelling service under 310.12, #2 AWG copper or 1/0 AWG aluminum (or copper-clad aluminum). 310.12 allows 83% of the 125 A rating, 103.75 A, in the 75 °C column of Table 310.16. Voltage drop is not included; long runs may need a larger conductor.
Why is that smaller than Table 310.16 gives for 125 amps?
Without the 310.12 allowance, 125 A in the 75 °C column needs #1 AWG copper or 2/0 AWG aluminum. 310.12 lets the service conductors of a one-family dwelling be sized at 83% of the rating.
Does this apply to commercial, three-phase or multifamily services?
No. This page covers only 120/240 V single-phase dwelling services that carry the entire load of a dwelling unit, 100 A to 400 A. Anything else is sized from Table 310.16 with the wire size calculator.
Does the 125 amp service answer assume 75 °C terminations?
Yes. The 310.12 result is read from the 75 °C column, so it assumes the service and meter terminations are listed or marked for 75 °C (110.14(C)). If any terminal is rated 60 °C, the conductor may need to be larger: for example #4 copper carries 85 A at 75 °C but only 70 A at 60 °C. Check the equipment markings.
Does the answer include ambient or conductor-count corrections?
No. The 310.12 answer applies no ambient (310.15(B)(1)) or adjustment (310.15(C)(1)) factors, and it is not a rule for the grounded or grounding conductors, which have their own rules. Use the wire size calculator for hot locations or bundled conductors.

You can read the NEC 2023 for free at NFPA free access. Need another load? Use the wire size calculator.