· 4 min read
Every conductor has resistance, so current flowing through it loses some voltage on the way to the load. On a short run you never notice. On a long run the load sees a lower voltage than the panel supplies: lights dim, motors run hot, and electronics can drop out. Calculating the drop before you pull wire is a few lines of arithmetic.
The voltage drop formula
Two formulas cover most runs. Use the first for single-phase and DC circuits, and the second for balanced three-phase circuits. Length is the one-way distance from the source to the load, in feet, and resistance is in ohms per 1000 ft.
Single-phase or DC: drop (V) = 2 x length x R x amps / 1000 Three-phase: drop (V) = sqrt(3) x length x R x amps / 1000 Percent drop = drop (V) / supply voltage x 100 Voltage at the load = supply voltage - drop (V)
Single-phase counts the length twice because the current goes out on one conductor and comes back on the other. Three-phase uses the square root of 3 instead because the three line currents are 120 degrees apart. If you run parallel sets, divide the result by the number of sets, since the current splits between them.
Where the resistance number comes from
The NEC gives you the resistance in Chapter 9. Table 8 lists the direct-current resistance of each conductor size. Table 9 lists the effective impedance for alternating current at the power factor the table assumes, which includes the conductor reactance and changes with the raceway: PVC, aluminum or steel conduit. Table 9 Note 2 says the Effective Z column is a line-to-neutral value, so the same length factors above apply with either table.
| Size | Table 8 dc resistance | Table 9 Effective Z, steel conduit |
|---|---|---|
| 12 AWG | 1.98 | 1.7 |
| 10 AWG | 1.24 | 1.1 |
| 8 AWG | 0.778 | 0.7 |
| 6 AWG | 0.491 | 0.45 |
| 4 AWG | 0.308 | 0.3 |
| 2 AWG | 0.194 | 0.2 |
| 1/0 AWG | 0.122 | 0.13 |
| 4/0 AWG | 0.0608 | 0.08 |
Table 8 is slightly conservative on the smaller sizes shown here: its figure is higher than Table 9 down through 4 AWG. From 2 AWG up in this table the Table 9 figure is the higher one, because reactance becomes a real share of the impedance, so it is the more realistic number for AC circuits on large conductors. Table 9 assumes a single power factor, so for a motor or other load with a different power factor, a full impedance calculation with the actual power factor is the better tool.
What the NEC says about voltage drop
The 3% and 5% numbers most people quote are not mandatory rules. They appear in Informational Notes: 3% for a branch circuit to the farthest outlet, and 5% for the feeder and branch circuit together. The notes are in 210.19 and in 215.2(A)(2) Informational Note No. 2 in NEC 2023, 215.4(A)(2) Informational Note No. 2 in NEC 2026. The 2023 and 2026 values are the same; only the feeder section number moved. Informational Notes are recommendations, so check whether the specification, another code or the equipment maker sets a hard limit on your job.
Worked examples
Example 1: long 120 V branch circuit
A 16 A load sits 100 ft from the panel on 12 AWG copper at 120 V. Using the Table 8 resistance of 1.98 ohms per 1000 ft:
Drop = 2 x 100 ft x 1.98 x 16 A / 1000 = 6.34 V Percent = 6.34 V / 120 V x 100 = 5.28 % Voltage at the load = 113.66 V
That is above the 3% figure recommended in the Informational Note. The smallest size that stays within 3% for these inputs is 8 AWG, which drops 2.49 V (2.07 %).
Example 2: three-phase feeder, DC against AC method
A 100 A load on a 480 V three-phase feeder, 250 ft one way, 1/0 AWG copper in steel conduit. With Table 8 (0.122 ohms per 1000 ft) the drop is 5.28 V, or 1.1 %. With Table 9 Effective Z (0.13 ohms per 1000 ft):
Drop = sqrt(3) x 250 ft x 0.13 x 100 A / 1000 = 5.63 V Percent = 5.63 V / 480 V x 100 = 1.17 % Voltage at the load = 474.37 V
Here the AC method gives the higher drop, which is why it is the better choice on larger conductors. Judged against the 5% combined feeder and branch circuit figure from the Informational Notes (the 3% figure is for the branch circuit, not a feeder figure), both results are within it, and that leaves room for the branch circuit drop. Any branch circuit drop downstream adds to the feeder figure.
Example 3: 240 V single-phase subpanel feed
A 50 A load 150 ft away on 6 AWG copper at 240 V (Table 8: 0.491 ohms per 1000 ft) drops 7.37 V, which is 3.07 % of 240 V and above the 3% figure. The smallest size within 3% is 4 AWG, dropping 4.62 V (1.93 %).
How to fix excessive voltage drop
- Upsize the conductor. Resistance falls as the size goes up, and this is the usual fix. A bigger wire is not free: check that the lugs and terminals accept it.
- Use parallel sets on larger feeders. The current splits between the sets, so the drop divides by the number of sets.
- Shorten the run, for example by moving the panel closer to the load.
- Use copper instead of aluminum at the same size. Aluminum has higher resistance per 1000 ft.
- Raise the supply voltage where the equipment allows it. The same load at 240 V draws half the current it does at 120 V, so the percent drop falls sharply.
A size picked for voltage drop must still meet ampacity, termination and overcurrent protection rules. Use the wire size calculator for those, and keep the larger of the two answers.
Frequently asked questions
- What is the formula for voltage drop?
- For single-phase or DC, drop in volts = 2 x one-way length x resistance per 1000 ft x amps / 1000. For three-phase, replace the 2 with the square root of 3. Percent drop is the drop divided by the supply voltage, times 100.
- Is 3% voltage drop required by the NEC?
- No. The 3% branch-circuit figure and the 5% combined figure appear only in Informational Notes, which are recommendations. A project specification or another code can still set a limit.
- Should I use Table 8 or Table 9 for voltage drop?
- Table 8 is the dc resistance and is simple to use. Table 9 is the AC effective impedance at an assumed power factor and depends on the raceway material, which makes it more realistic on larger conductors. Both are line-to-neutral values, so the same length factors apply.
- Why is length doubled for single-phase voltage drop?
- Current flows out on one conductor and returns on the other, so the circuit resistance is that of twice the one-way length.
References
- NEC 2023 & 2026 Chapter 9, Table 8 (conductor properties, dc resistance)
- NEC 2023 & 2026 Chapter 9, Table 9 (a.c. resistance and reactance, Effective Z column, and Note 2)
- NEC 2023 & 2026 210.19 Informational Note and 215.2(A)(2) Informational Note No. 2 in NEC 2023, 215.4(A)(2) Informational Note No. 2 in NEC 2026 (voltage drop recommendations)
For reference only. Always verify with the NEC edition adopted by your AHJ.